MÉTODOS PARA CORREÇÃO DAS DISTORÇÕES DA FORMA DE ONDA SECUNDÁRIA CAUSADAS PELA SATURAÇÃO DE TRANSFORMADORES DE CORRENTE PARA SERVIÇO DE PROTEÇÃO / METHODS FOR CORRECTION OF SECONDARY WAVEFORM DISTORTIONS CAUSED BY SATURATION OF CURRENT TRANSFORMERS FOR PROTECTIVE RELAYING PURPOSES
AUTOR(ES)
Eduardo Machado dos Santos
FONTE
IBICT - Instituto Brasileiro de Informação em Ciência e Tecnologia
DATA DE PUBLICAÇÃO
18/02/2011
RESUMO
This work aims to evaluate the performance of some methods used to detect and correct the distorted portions of the secondary current signal waveform, which occur due to the core saturation of current transformers. Such methods are presented didactically divided among techniques existing in the specialized literature and new methodologies proposed. Involving various mathematical tools, methods of correction and detection were combined for the analyzed cases. Computer simulations of faults were made to obtain secondary current signals distorted by saturation, allowing the evaluation of these methodologies. The detection methods were evaluated in terms of the ability to identify saturation intervals and speed response. Moreover, the correction techniques were evaluated in terms of compensation accuracy and their processing time. Transient error calculations and the use of a full cycle Fourier filter were the basis for the qualitative analysis of the correction techniques performance. In each case analyzed, different performances were verified for the combinations tested. It was found that differences in detection time instants of the distorted portions provide different rates of error to the methodologies that are associated with saturation detectors. In this context, one of the techniques proposed for detection of distorted sections showed good precision, ensuring low errors for one of the associated correction methodologies in all the analyzed cases. Also, it was found that methods based on Least Squares have good accuracy for the correction of signals distorted by saturation.
ASSUNTO(S)
correção detecção forma de onda distorcida intervalos de saturação proteção de sistemas elétricos de potência transformadores de corrente engenharia civil correction detection distorted waveform electric power systems protection saturation intervals current transformer
ACESSO AO ARTIGO
http://coralx.ufsm.br/tede/tde_busca/arquivo.php?codArquivo=3828Documentos Relacionados
- Projeto diferencial de geradores síncronos: o uso de redes neurais artificiais para identificação e correção da saturação dos transformadores de corrente
- ANÁLISE DE TRANSFORMADORES DE CORRENTE PARA MEDIÇÃO
- Redes neurais artificiais recorrentes aplicadas na correção de sinais distorcidos pela saturação de transformadores de corrente
- ANÁLISE DE CODIFICADORES DE FORMA DE ONDA PARA SINAIS DE VOZ E DADOS
- Sistema híbrido inteligente para o monitoramento e proteção de transformadores de potência