Avaliação de diferentes métodos para a determinação de cobre em óleo mineral isolante por espectrometria de absorção atômica com forno de grafite

AUTOR(ES)
FONTE

Quím. Nova

DATA DE PUBLICAÇÃO

2014-06

RESUMO

This aim of this work was to compare two methods for copper determination in insulating oils from power transformers by GFAAS. The first method was extraction induced by emulsion breaking, which determined the preconcentration of copper in an aqueous solution and exhibited a limit of quantification of 0.27 µg L-1. Also, a second method based on the direct introduction of samples into GFAAS in the form of detergent emulsions, prepared with Triton X-114 and HNO3, was investigated. In this case, the limit of quantification was 1.7 µg L-1. Seven samples of used oils were successfully analyzed by both methods.